Table 1. Factory-Recommended Branch Circuit Protection: 200 V Class (ND)

Drive Model

Maximum Applicable Motor Output

kW (HP)

Input Current Rating

A

Semiconductor Protection Fuse Rated Current

Manufacturer: EATON/Bussmann

2004

0.75 (0.75)

4.8

FWH-45B

2006

1.1 (1.5)

6.7

FWH-45B

2008

1.5 (2)

8.9

FWH-45B

2010

2.2 (3)

12.7

FWH-45B

2012

3 (4)

17

FWH-50B

FWH-80B1

2018

3.7 (5)

20.7

FWH-80B

FWH-100B1

2021

5.5 (7.5)

30

FWH-80B

FWH-100B1

2030

7.5 (10)

40.3

FWH-125B

2042

11 (15)

52

FWH-150B

2056

15 (20)

78.4

FWH-200B

2070

18.5 (25)

96

FWH-225A

2082

22 (30)

114

FWH-225A

FWH-250A>1

2110

30 (40)

111

FWH-225A

FWH-2501

2138

37 (50)

136

FWH-275A

FWH-300A1

2169

45 (60)

164

FWH-275A

FWH-350A1

2211

55 (75)

200

FWH-325A

FWH-450A1

2257

75 (100)

271

FWH-600A

2313

90 (125)

324

FWH-800A

2360

110 (150)

394

FWH-1000B

2415

-

-

-

 
Table 2. Factory-Recommended Branch Circuit Protection: 200 V Class (HD)

Drive Model

Maximum Applicable Motor Output

kW (HP)

Input Current Rating

A

Semiconductor Protection Fuse Rated Current

Manufacturer: EATON/Bussmann

2004

0.55 (0.5)

3.6

FWH-45B

2006

0.75 (1)

4.8

FWH-45B

2008

1.1 (1.5)

6.7

FWH-45B

2010

1.5 (2)

8.9

FWH-45B

2012

2.2 (3)

12.7

FWH-50B

FWH-80B1

2018

3 (4)

17

FWH-80B

FWH-100B1

2021

3.7 (5)

20.7

FWH-80B

FWH-100B1

2030

5.5 (7.5)

30

FWH-125B

2042

7.5 (10)

40.3

FWH-150B

2056

11 (15)

58.2

FWH-200B

2070

15 (20)

78.4

FWH-225A

2082

18.5 (25)

96

FWH-225A

FWH-250A1

2110

22 (30)

82

FWH-225A

FWH-250A1

2138

30 (40)

111

FWH-275A

FWH-300A1

2169

37 (50)

136

FWH-275A

FWH-350A1

2211

45 (60)

164

FWH-325A

FWH-450A1

2257

55 (75)

200

FWH-600A

2313

75 (100)

271

FWH-800A

2360

90 (125)

324

FWH-1000B

2415

110 (150)

394

FWH-1000B

1

Yaskawa recommends a fuse with a large rated current for applications with repeated loads.