YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
A1-01
(0101)
RUN
Access Level Selection
Sets user access to parameters. The access level controls which parameters the keypad will display, and which parameters the user can set.
2
(0 - 3)
Access to A1-00, A1-01, A1-04 [Password], and the U Monitors.
Access to A1-00, A1-01, A1-04, and A2-01 to A2-32 [User Parameters 1 to 32].
Access to all parameters, but not Expert Mode parameters.
Access to all parameters including Expert Mode parameters.
Table 1 shows which keypad screens are available for each A1-01 settings.
Mode
Keypad Screen
A1-01 [Access Level Selection] Setting
0
1
3
Drive Mode
Monitors
Yes
Programming Mode
Parameters
User Custom Parameters
No
Parameter Backup/Restore
Modified Parameters/Fault Log
Auto-Tuning
Initial Setup Screen
Diagnostic Tools
When you use A1-04 and A1-05 [Password Setting] to set a password, you cannot change the values set in A1-01 to A1-03, A1-06, A1-07,or A2-01 to A2-32.
When H1-xx = 1B [MFDI Function Select = Program Lockout], you must activate the terminal to change parameter settings.
When you use MEMOBUS/Modbus communications, you must send the Enter command from the controller to the drive and complete the serial communication write process before you can use the keypad to change parameter settings.