Jump to main content

A1-06: Application Preset

No.

(Hex.)

Name

Description

Default

(Range)

A1-06

(0127)

Application Preset

Sets the drive to operate in selected application conditions.

0

(0 - 8)

The drive software contains the application presets shown below. Set A1-06 to align with the application to let the drive automatically set the best parameter settings for the selected application. The drive saves parameters that you frequently use the application in parameters A2-01 to A2-16 [User Parameters 1 to 16] for easy configuration and reference in Setup Mode.

  • Water supply pump

  • Conveyor

  • Exhaust fan

  • HVAC fan

  • Air compressor

  • Crane (hoist)

  • Crane (traveling)

Note:
  • Before you set A1-06, make sure that you set A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization] to initialize parameters.

  • After you set A1-06 for a hoist application (A1-06 = 6 or 7), make sure that you do Auto-Tuning.

  • It is not possible to change the A1-06 value. To set an application preset, set A1-03 = 2220 to initialize parameters, then set this parameter. If initializing all parameters will cause a problem, do not change the settings.

    If you set A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms] to set parameters to A2-17 to A2-32 [User Parameters 17 to 32] automatically, the drive will reset these parameters when you change the A1-06 setting.

0
General-purpose

The drive saves the parameters in Table 1 as User Parameters.

Table 1. Parameters Saved as User Parameters with the General-purpose Preset

User Parameter No.

Parameter No. Saved

Name

A2-01

A1-02

Control Method Selection

A2-02

b1-01

Frequency Reference Selection 1

A2-03

b1-02

Run Command Selection 1

A2-04

b1-03

Stopping Method Selection

A2-05

C1-01

Acceleration Time 1

A2-06

C1-02

Deceleration Time 1

A2-07

C6-01

Normal / Heavy Duty Selection

A2-08

C6-02

Carrier Frequency Selection

A2-09

d1-01

Reference 1

A2-10

d1-02

Reference 2

A2-11

d1-03

Reference 3

A2-12

d1-04

Reference 4

A2-13

d1-17

Jog Reference

A2-14

E1-01

Input AC Supply Voltage

A2-15

E1-03

V/f Pattern Selection

A2-16

E1-04

Maximum Output Frequency

A2-17

E1-05

Maximum Output Voltage

A2-18

E1-06

Base Frequency

A2-19

E1-09

Minimum Output Frequency

A2-20

E1-13

Base Voltage

A2-21

E2-01

Motor Rated Current (FLA)

A2-22

E2-04

Motor Pole Count

A2-23

E2-11

Motor Rated Power

A2-24

H4-02

Terminal AM Analog Output Gain

A2-25

L1-01

Motor Overload (oL1) Protection

A2-26

L3-04

Stall Prevention during Decel

1
Water Supply Pump 2

The drive automatically sets the parameters in Table 2 for a water supply pump application.

Table 2. Best Parameter Settings for Water Supply Pump Applications

No.

Name

Optimal Value

A1-02

Control Method Selection

0: V/f Control

b1-04

Reverse Operation Selection

1: Reverse Disabled

C1-01

Acceleration Time 1

1.0 s

C1-02

Deceleration Time 1

1.0 s

C6-01

Normal / Heavy Duty Selection

1: Normal Duty Rating

E1-03

V/f Pattern Selection

F: Custom

E1-07

Mid Point A Frequency

30.0 Hz

E1-08

Mid Point A Voltage

50.0 V

L2-01

Power Loss Ride Through Select

1: Enabled

L3-04

Stall Prevention during Decel

1: General Purpose

The drive saves the parameters in Table 3 as User Parameters.

Table 3. Parameters Saved as User Parameters with the Water Supply Pump Preset

User Parameter No.

Parameter No. Saved

Name

A2-01

b1-01

Frequency Reference Selection 1

A2-02

b1-02

Run Command Selection 1

A2-03

b1-04

Reverse Operation Selection

A2-04

C1-01

Acceleration Time 1

A2-05

C1-02

Deceleration Time 1

A2-06

E1-03

V/f Pattern Selection

A2-07

E1-07

Mid Point A Frequency

A2-08

E1-08

Mid Point A Voltage

A2-09

E2-01

Motor Rated Current (FLA)

A2-10

H1-05

Terminal S5 Function Selection

A2-11

H1-06

Terminal S6 Function Selection

A2-12

H1-07

Terminal S7 Function Selection

A2-13

L5-01

Number of Auto-Restart Attempts

2
Conveyor

The drive automatically sets the parameters in Table 4 for a conveyor application.

Table 4. Best Parameter Settings for Conveyor Applications

No.

Name

Optimal Value

A1-02

Control Method Selection

0: V/f Control

C1-01

Acceleration Time 1

3.0 s

C1-02

Deceleration Time 1

3.0 s

C6-01

Normal / Heavy Duty Selection

0: Heavy Duty Rating

L3-04

Stall Prevention during Decel

1: General Purpose

The drive saves the parameters in Table 5 as User Parameters.

Table 5. Parameters Saved as User Parameters with the Conveyor Preset

User Parameter No.

Parameter No. Saved

Name

A2-01

A1-02

Control Method Selection

A2-02

b1-01

Frequency Reference Selection 1

A2-03

b1-02

Run Command Selection 1

A2-04

C1-01

Acceleration Time 1

A2-05

C1-02

Deceleration Time 1

A2-06

E2-01

Motor Rated Current (FLA)

A2-07

L3-04

Stall Prevention during Decel

3
Exhaust Fan

The drive automatically sets the parameters in Table 6 for an exhaust fan application.

Table 6. Best Parameter Settings for Exhaust Fan Applications

No.

Name

Optimal Value

A1-02

Control Method Selection

0: V/f Control

b1-04

Reverse Operation Selection

1: Reverse Disabled

C6-01

Normal / Heavy Duty Selection

1: Normal Duty Rating

E1-03

V/f Pattern Selection

F: Custom

E1-07

Mid Point A Frequency

30.0 Hz

E1-08

Mid Point A Voltage

50.0 V

L2-01

Power Loss Ride Through Select

1: Enabled

L3-04

Stall Prevention during Decel

1: General Purpose

The drive saves the parameters in Table 7 as User Parameters.

Table 7. Parameters Saved as User Parameters with the Exhaust Fan Preset

User Parameter No.

Parameter No. Saved

Name

A2-01

b1-01

Frequency Reference Selection 1

A2-02

b1-02

Run Command Selection 1

A2-03

b1-04

Reverse Operation Selection

A2-04

b3-01

Speed Search at Start Selection

A2-05

C1-01

Acceleration Time 1

A2-06

C1-02

Deceleration Time 1

A2-07

E1-03

V/f Pattern Selection

A2-08

E1-07

Mid Point A Frequency

A2-09

E1-08

Mid Point A Voltage

A2-10

E2-01

Motor Rated Current (FLA)

A2-11

H1-05

Terminal S5 Function Selection

A2-12

H1-06

Terminal S6 Function Selection

A2-13

H1-07

Terminal S7 Function Selection

A2-14

L5-01

Number of Auto-Restart Attempts

4
HVAC Fan

The drive automatically sets the parameters in Table 8 for an HVAC fan application.

Table 8. Best Parameter Settings for HVAC Fan Applications

No.

Name

Optimal Value

A1-02

Control Method Selection

0: V/f Control

b1-04

Reverse Operation Selection

1: Reverse Disabled

b1-17

Run Command at Power Up

1: Accept Existing RUN Command

C6-01

Normal / Heavy Duty Selection

1: Normal Duty Rating

C6-02

Carrier Frequency Selection

3: 8.0 kHz (6.0 kHz for AOLV/PM)

H2-03

Terminal P2-C2 Function Selection

39: Watt Hour Pulse Output

L2-01

Power Loss Ride Through Select

2: Enabled while CPU Power Active

L8-03

Overheat Pre-Alarm Selection

4: Operate at Reduced Speed (L8-19)

The drive saves the parameters in Table 9 as User Parameters.

Table 9. Parameters Saved as User Parameters with the HVAC Fan Preset

User Parameter No.

Parameter No. Saved

Name

A2-01

b1-01

Frequency Reference Selection 1

A2-02

b1-02

Run Command Selection 1

A2-03

b1-03

Stopping Method Selection

A2-04

b1-04

Reverse Operation Selection

A2-05

C1-01

Acceleration Time 1

A2-06

C1-02

Deceleration Time 1

A2-07

C6-02

Carrier Frequency Selection

A2-08

d2-01

Frequency Reference Upper Limit

A2-09

d2-02

Frequency Reference Lower Limit

A2-10

E1-03

V/f Pattern Selection

A2-11

E1-04

Maximum Output Frequency

A2-12

E2-01

Motor Rated Current (FLA)

A2-13

H3-11

Terminal A2 Gain Setting

A2-14

H3-12

Terminal A2 Bias Setting

A2-15

L2-01

Power Loss Ride Through Select

A2-16

o4-12

kWh Monitor Initialization

5
Air Compressor

The drive automatically sets the parameters in Table 10 for an air compressor application.

Table 10. Best Parameter Settings for Air Compressor Applications

No.

Name

Optimal Value

A1-02

Control Method Selection

0: V/f Control

b1-04

Reverse Operation Selection

1: Reverse Disabled

C1-01

Acceleration Time 1

5.0 s

C1-02

Deceleration Time 1

5.0 s

C6-01

Normal / Heavy Duty Selection

0: Heavy Duty Rating

E1-03

V/f Pattern Selection

F: Custom

L2-01

Power Loss Ride Through Select

1: Enabled

L3-04

Stall Prevention during Decel

1: General Purpose

The drive saves the parameters in Table 11 as User Parameters.

Table 11. Parameters Saved as User Parameters with the Air Compressor Preset

User Parameter No.

Parameter No. Saved

Name

A2-01

b1-01

Frequency Reference Selection 1

A2-02

b1-02

Run Command Selection 1

A2-03

b1-04

Reverse Operation Selection

A2-04

C1-01

Acceleration Time 1

A2-05

C1-02

Deceleration Time 1

A2-06

E1-03

V/f Pattern Selection

A2-07

E1-07

Mid Point A Frequency

A2-08

E1-08

Mid Point A Voltage

A2-09

E2-01

Motor Rated Current (FLA)

6
Crane (Hoist)

The drive automatically sets the parameters in Table 12 for a hoist application.

Note:

Make sure that you do Auto-Tuning after you set A1-06 for a hoist application. Refer to Notes for Elevator or Lift Applications for hoist (elevator) instructions.

Table 12. Best Parameter Settings for Hoist Applications

No.

Name

Optimal Value

A1-02

Control Method Selection

2: Open Loop Vector

b1-01

Frequency Reference Selection 1

0: Keypad

b6-01

Dwell Reference at Start

3.0 Hz

b6-02

Dwell Time at Start

0.3 s

C1-01

Acceleration Time 1

3.0 s

C1-02

Deceleration Time 1

3.0 s

C6-01

Normal / Heavy Duty Selection

0: Heavy Duty Rating

C6-02

Carrier Frequency Selection

2: 5.0 kHz (4.0 kHz for AOLV/PM)

d1-01

Reference 1

6.00 Hz

d1-02

Reference 2

30.00 Hz

d1-03

Reference 3

60.00 Hz

E1-03

V/f Pattern Selection

F: Custom

H2-01

Term MA/MB-MC Function Selection

5: Frequency Detection 2

H2-02

Terminal P1-C1 Function Selection

37: During Frequency Output

L2-03

Minimum Baseblock Time

0.3 s

L3-04

Stall Prevention during Decel

0: Disabled

L4-01

Speed Agree Detection Level

2.0 Hz

L4-02

Speed Agree Detection Width

0.0 Hz

L6-01

Torque Detection Selection 1

8: UL @ RUN - Fault

L6-02

Torque Detection Level 1

2%

L6-03

Torque Detection Time 1

0.5 s

L8-05

Input Phase Loss Protection Sel

1: Enabled

L8-07

Output Phase Loss Protection Sel

1: Fault when One Phase is Lost

L8-41

High Current Alarm Selection

1: Enabled

The drive saves the parameters in Table 13 as User Parameters.

Table 13. Parameters Saved as User Parameters with the Hoist Preset

User Parameter No.

Parameter No. Saved

Name

A2-01

A1-02

Control Method Selection

A2-02

b1-01

Frequency Reference Selection 1

A2-03

b6-01

Dwell Reference at Start

A2-04

b6-02

Dwell Time at Start

A2-05

C1-01

Acceleration Time 1

A2-06

C1-02

Deceleration Time 1

A2-07

C6-02

Carrier Frequency Selection

A2-08

d1-01

Reference 1

A2-09

d1-02

Reference 2

A2-10

d1-03

Reference 3

A2-11

E1-08

Mid Point A Voltage

A2-12

H2-01

Term MA/MB-MC Function Selection

A2-13

L1-01

Motor Overload (oL1) Protection

A2-14

L4-01

Speed Agree Detection Level

A2-15

L6-02

Torque Detection Level 1

A2-16

L6-03

Torque Detection Time 1

7
Crane (Traveling)

The drive automatically sets the parameters in Table 14 for a traveling application.

Table 14. Optimal Settings for Traveling Applications

No.

Name

Optimal Value

A1-02

Control Method Selection

0: V/f Control

b1-01

Frequency Reference Selection 1

0: Keypad

C1-01

Acceleration Time 1

3.0 s

C1-02

Deceleration Time 1

3.0 s

C6-01

Normal / Heavy Duty Selection

0: Heavy Duty Rating

C6-02

Carrier Frequency Selection

2: 5.0 kHz (4.0 kHz for AOLV/PM)

d1-01

Reference 1

6.00 Hz

d1-02

Reference 2

30.00 Hz

d1-03

Reference 3

60.00 Hz

H1-05

Terminal S5 Function Selection

3: Multi-Step Speed Reference 1

H1-06

Terminal S6 Function Selection

4: Multi-Step Speed Reference 2

H2-01

Term MA/MB-MC Function Selection

37: During Frequency Output

H2-02

Terminal P1-C1 Function Selection

37: During Frequency Output

L3-04

Stall Prevention during Decel

0: Disabled

L8-05

Input Phase Loss Protection Sel

1: Enabled

L8-07

Output Phase Loss Protection Sel

1: Fault when One Phase is Lost

L8-41

High Current Alarm Selection

1: Enabled

The drive saves the parameters in Table 15 as User Parameters.

Table 15. Parameters Saved as User Parameters with the Traveling Preset

User Parameter No.

Parameter No. Saved

Name

A2-01

b1-01

Frequency Reference Selection 1

A2-02

C1-01

Acceleration Time 1

A2-03

C1-02

Deceleration Time 1

A2-04

C6-02

Carrier Frequency Selection

A2-05

d1-01

Reference 1

A2-06

d1-02

Reference 2

A2-07

d1-03

Reference 3

A2-08

E2-01

Motor Rated Current (FLA)

A2-09

H1-05

Terminal S5 Function Selection

A2-10

H1-06

Terminal S6 Function Selection

A2-11

H2-01

Term MA/MB-MC Function Selection

A2-12

L1-01

Motor Overload (oL1) Protection

8
Conveyor 2

The drive automatically sets the parameters in Table 16 for a conveyor 2 application.

Table 16. Best Parameter Settings for Conveyor 2 Application

No.

Name

Optimal Value

A1-02

Control Method Selection

0: V/f Control

C1-01

Acceleration Time 1

3.0 s

C1-02

Deceleration Time 1

3.0 s

C6-01

Normal / Heavy Duty Selection

0: Heavy Duty Rating

L3-04

Stall Prevention during Decel

7: Overexcitation/High Flux 3

n3-13

OverexcitationBraking (OEB) Gain

1.40

n3-21

HSB Current Suppression Level

150

The drive saves the parameters in Table 17 as User Parameters.

Table 17. Parameters Saved as User Parameters with the Conveyor 2 Preset

User Parameter No.

Parameter No. Saved

Name

A2-01

A1-02

Control Method Selection

A2-02

b1-01

Frequency Reference Selection 1

A2-03

b1-02

Run Command Selection 1

A2-04

C1-01

Acceleration Time 1

A2-05

C1-02

Deceleration Time 1

A2-06

E2-01

Motor Rated Current (FLA)

A2-07

L3-04

Stall Prevention during Decel

A2-08

n3-13

OverexcitationBraking (OEB) Gain

A2-09

n3-21

HSB Current Suppression Level