No.

(Hex.)

Name

Description

Default

(Range)

A1-07

(0128)

DriveWorksEZ Function Selection

Sets the drive to operate with DriveWorksEZ.

0

(0 - 2)

DriveWorksEZ is a simple visual programming tool that lets you connect function blocks to customize the drive and add PLC functions.

Note:
  • DriveWorksEZ will overwrite drive settings when it uses MFDI/MFDO and MFAI/MFAO. When you use DriveWorksEZ to make changes to the drive, the changes will stay after you disable DriveWorksEZ.

  • For more information about DriveWorksEZ, contact Yaskawa or your nearest sales representative.

0
DWEZ Disabled
 
1
DWEZ Enabled
 
2
Enabled/Disabled wDigital Input

Set H1-xx = 9F [MFDI Function Select = DWEZ Disable]. Deactivate the digital input to enable programs made with DriveWorksEZ. Activate the terminal to disable the programs.

If A1-07 = 1 [DriveWorksEZ Function Selection = DWEZ Enabled], the drive will continue to disable DWEZ when these conditions are true:

  • Drive is not in operation

  • The MFDI terminals set for H1-xx = 9F activate.