YASKAWA AC Drive GA700 High Performance Type Technical Manual
Set L4-07 = 0 [Speed Agree Detection Selection = No Detection during Baseblock] to open and close the holding brake.
When L4-07 = 1 [Detection Always Enabled], the output frequency increases when you input the Run command although the external baseblock command is input. Because of this, speed detection operates and will open the brake signal.
Set Related Parameters
Table 1 shows examples of parameter settings to use the terminal P2-C2 as the holding brake open and close signal.
Brake Open and Close Signal
Brake Open and Close Level Adjust
Applicable Control Methods (A1-02 Settings)
Signal Name
Parameter Settings
V/f
(0)
OLV
(2)
Frequency (FOUT) Detection 2
L4-07 = 0
Speed Agree Detection Level
L4-01 = 1.0 Hz to 3.0 Hz1
x
H2-03 = 5
Speed Agree Detection Width
L4-02 = 0.0 Hz to 0.5 Hz
When A1-02 = 2 [Open Loop Vector], it is the usual setting range. When A1-02 = 0 [V/f Control], set L4-01 to the rated slip frequency of the motor + approximately 0.5 Hz. If you set the value too low, motor torque will not be sufficient and it will cause motor rollback. Set the parameter to agree with these conditions at the same time. If you set the value too high, it will cause overshoot at start.
L4-01 > E1-09 [Minimum Output Frequency]
L4-01 > L4-02 [Speed Agree Detection Width]
Use L4-02 to adjust the detection width of Frequency Detection 2. If rollback occurs when the motor stops, change the frequency to approximately 0.1 Hz.