No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b1-07
(0186)
|
LOCAL/REMOTE Run Selection
|
   
Sets drive response to an existing Run command when the drive receives a second Run command from a different location.
|
0
(0, 1)
|
This parameter interlocks the drive to help prevent accidents that can occur if the motor starts to rotate because the Run command source changed.
To switch the RUN command source, push
on the keypad or set H1-xx = 1, 2 [MFDI Function Selection = LOCAL/REMOTE Selection, External Reference 1/2 Selection] and activate/deactivate the terminal.
- 0
- Disregard Existing RUN Command
-
If a Run command is enabled when you switch between Run command sources, the drive will not operate the motor.
When the drive is operating the motor, turn OFF the Run command to stop the motor. Enter the Run command again to start operation.
- 1
- Accept Existing RUN Command
-
If a Run command is enabled when you switch between Run command sources, the drive will start to operate the motor or continue to operate the motor.
| Warning |
|
Sudden Movement Hazard
When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize Parameters = 3-Wire Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] (default).
If you do not correctly set the drive parameters for 3-Wire operation before you energize the drive, the motor can suddenly rotate when you energize the drive.
|