No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b1-08
(0187)
|
Run Command Select in PRG Mode
|
   
Sets the conditions for the drive to accept a Run command entered from an external source when using the keypad to set parameters.
|
0
(0 - 2)
|
As a safety precaution, when the drive is in Programming Mode, it will not respond to a Run command.
This parameter helps prevent accidents that can occur if the motor starts to rotate because the drive received a Run command from an external source while the user is programming the drive. You can also set the drive to not show the Programming Mode when a Run command is active.
Note:
Refer to this table for Drive Mode and Programming Mode functions.
|
Mode
|
Keypad Screen
|
Function
|
|
Drive Mode
|
Monitors
|
Sets monitor display.
|
|
Programming Mode
|
Parameters
|
Changes parameter settings.
|
|
User Custom Parameters
|
Shows the User Parameters.
|
|
Parameter Backup/Restore
|
Saves parameters to the keypad as backup.
|
|
Modified Parameters/Fault Log
|
Shows modified parameters and fault history.
|
|
Auto-Tuning
|
Auto-Tunes the drive.
|
|
Initial Setup Screen
|
Changes initial settings.
|
|
Diagnostic Tools
|
Sets data logs and backlight.
|
- 0
- Disregard RUN while Programming
-
The drive does not accept the Run command when setting the parameters in the Programming Mode.
- 1
- Accept RUN while Programming
-
The drive accepts a Run command entered from an external source when setting the parameters in Programming Mode.
- 2
- Allow Programming Only at Stop
-
The drive does not allow the user to enter the Programming Mode while the drive is operating. The keypad does not display the Programming Mode while the drive is operating.