b1-15
(01C4)
|
Frequency Reference Selection 2
|
   
Sets the input method for frequency reference 2.
|
0
(0 - 4)
|
This parameter is enabled when H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection] is activated.
Note:
-
Push
on the keypad to set the input mode to LOCAL and use the keypad to enter the frequency reference.
-
If the frequency reference is 0 Hz or less than or equal to the value set in E1-09 [Minimum Output Frequency] and the drive receives the Run command, the RUN LED on the keypad will flash. Examine the setting for the frequency reference input and enter a value more than or equal to E1-09.
- 0
- Keypad
-
Use the keypad to enter the frequency reference.
Use
and
on the keypad to change the frequency reference.
- 1
- Analog Input
-
Use MFAI terminals A1 and A2 to input an analog frequency reference with a voltage or current input signal.
Changing between Master and Auxiliary Frequency References
Use the multi-step speed reference function to change the frequency reference input between terminals A1 and A2.
- 2
- Memobus/Modbus Communications
-
Use MEMOBUS/Modbus communications to enter the frequency reference.
- 3
- Option PCB
-
Use a communications option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If you set b1-15 = 3 but you do not connect an option card, oPE03 [Multi-Function Input Setting Err] will flash on the keypad.
- 4
- Pulse Train Input
-
Use a pulse train signal from the pulse train input terminal RP to enter the frequency reference.
Do this procedure to make sure that the pulse train signal is operating correctly.
-
Set b1-15 = 4, H6-01 = 0 [Terminal RP Pulse Train Function = Frequency Reference].
-
Set H6-02 [Terminal RP Frequency Scaling] to the number of pulses that determine 100% of the frequency reference.
-
The terminal set in H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection] is activated.
-
Enter a pulse train signal on the terminal RP and make sure that the keypad shows a correct frequency reference.