No.

(Hex.)

Name

Description

Default

(Range)

b1-16

(01C5)

Run Command Selection 2

Sets the input method for Run Command 2 when the user switches the control circuit terminals ON/OFF to change the Run command source.

0

(0 - 3)

Activate H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection] to enable this parameter.

0
Keypad

Use the keypad to enter the Run command.

You can use the JOG operation or the FWD/REV commands from the keypad.

Note:

The [LOCAL/REMOTE LED] is on while the keypad is the Run command source.

1
Digital Input

Use the control circuit terminals to enter the Run command. Select the input method for the Run command with an H1-xx parameter.

Set H1-xx = 0, 40 to 43 [3-Wire Sequence, Run Command (2-Wire Sequence)]. The default setting is 2-wire sequence 1.

  • 2-wire Sequence 1

    This sequence has two input types: FWD/Stop and REV/Stop. Set A1-03 = 2220 [Initialize Parameters = 2-Wire Initialization] to initialize the drive and set terminals S1 and S2 for a 2-wire sequence.

  • 2-wire Sequence 2

    This sequence has two input types: Run/Stop and FWD/REV.

  • 3-Wire Sequence

    This sequence has three input types: Run, Stop, and FWD/REV. Set A1-03 = 3330 [Initialize Parameters = 3-Wire Initialization] to initialize the drive and set terminals S1, S2, and S5 for a 3-wire sequence.

2
Memobus/Modbus Communications

Use MEMOBUS/Modbus communications to enter the Run command.

3
Option PCB

Use a communications option card or input option card connected to the drive to enter the Run command.

Refer to the instruction manual included with the option card to install and set the option card.

Note:

If b1-16 = 3 but no option card is connected, then oPE03 [Multi-Function Input Setting Err] will flash on the keypad.