No.

(Hex.)

Name

Description

Default

(Range)

b1-17

(01C6)

Run Command at Power Up

Sets drive response when the CPU changes from de-energized to energized and there is an active Run command. Set this parameter in applications where energizing or de-energizing the drive enables the Run command. When the CPU stays energized during loss of power, L2-01 [Power Loss Ride Through Select] sets operation.

0

(0, 1)

0
Disregard Existing RUN Command

The drive does not start to operate the application when you apply power, even when there is an existing Run command.

Enter the Run command again to operate the application.

Note:

When you energize the drive, [RUN LED] on the keypad will flash quickly if the Run command is already enabled from an external source.

1
Accept Existing RUN Command

When there is an existing Run command, the drive starts to operate the application when you apply power.