No.

(Hex.)

Name

Description

Default

(Range)

b1-35

(1117)

Expert

Digital Input Deadband Time

Sets the deadband time for MFDIs.

0.0 ms

(0.0 to 100.0 ms)

When the on/off time for MFDIs is longer than the time set in b1-35, the drive activates the MFDI. Set this parameter to prevent malfunctions caused by relay chattering for applications in which relays send input to MFDI terminals.