No.

(Hex.)

Name

Description

Default

(Range)

b2-03

(018B)

DC Inject Braking Time at Start

Sets the DC Injection Braking Time at stop.

0.00 s

(0.00 - 10.00 s)

This function stops then restarts a coasting motor and increases motor flux to make high starting torque (a process called initial excitation). Set this parameter to 0.00 to disable the function.

Note:

To restart a coasting motor, use DC Injection Braking to stop and then restart the motor, or enable Speed Search. Enable DC Injection Braking or Speed Search to prevent ov [Overvoltage] or oC [Overcurrent] faults.