No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b2-03
(018B)
|
DC Inject Braking Time at Start
|
   
Sets the DC Injection Braking Time at stop.
|
0.00 s
(0.00 - 10.00 s)
|
This function stops then restarts a coasting motor and increases motor flux to make high starting torque (a process called initial excitation). Set this parameter to 0.00 to disable the function.
Note:
To restart a coasting motor, use DC Injection Braking to stop and then restart the motor, or enable Speed Search. Enable DC Injection Braking or Speed Search to prevent ov [Overvoltage] or oC [Overcurrent] faults.