No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b2-12
(01BA)
|
Short Circuit Brake Time @ Start
|
   
Sets the Short Circuit Braking time at start.
|
0.00 s
(0.00 - 25.50 s)
|
This function stops and restarts a coasting PM motor. The drive short circuits all the three motor phases to make braking torque in the motor.
Set this parameter to 0.00 to disable the function.
Note:
-
Short circuit Braking will let external forces rotate the PM motor. Use DC Injection Braking to prevent motor rotation from external forces.
-
Motor speed and load conditions can make it necessary to install a dynamic braking option on the drive.