No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b2-13
(01BB)
|
Short Circuit Brake Time @ Stop
|
   
Sets the Short Circuit Braking time at stop.
|
A1-02 = 8: 0.00 s
Other than A1-02 = 8: 0.50 s
(0.00 - 25.50 s)
|
This function fully stops a PM motor with a large inertia during deceleration and will not let the inertia continue to rotate the motor.
Short Circuit Braking operates for the time set in b2-13 when output frequency is less than the value set in b2-01 [DC Injection/Zero SpeedThreshold] or E1-09 [Minimum Output Frequency].
Set this parameter to 0.00 to disable the function.
Note:
Motor speed and load conditions can make it necessary to install a dynamic braking option on the drive.