No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b2-18
(0177)
|
Short Circuit Braking Current
|
   
Sets the Short Circuit Braking Current as a percentage of the motor rated current.
|
100.0%
(0.0 - 200.0%)
|
The Short Circuit Braking current cannot be higher than the drive rated current, although you can use b2-18 to set a higher current level. The maximum rated current is 120% when the drive is set for Normal Duty (C6-01 = 1 [Normal Duty Rating]). The maximum rated current is 150% when the drive is set for Heavy Duty (C6-01 = 0 [Heavy Duty Rating]).