No. (Hex.) Name Description Default (Range) b3-01 (0191) Speed Search at Start Selection Sets the Speed Search at Start function so the drive will do Speed Search with each Run command. Determined by A1-02 (0, 1) 0 Disabled Enter a Run command to start to operate the drive at the minimum output frequency. When the Run command is enabled and the Speed Search from Fmax or Fref [H1-xx = 61, 62] is input from a multi-function input terminal, the drive will do Speed Search and start to operate the motor. 1 Enabled Enter the Run command to do Speed Search. The drive completes Speed Search, then starts to operate the motor.