No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b3-24
(01C0)
|
Speed Search Method Selection
|
   
Sets the Speed Search method when you start the motor or when you restore power after a momentary power loss.
|
2
(1, 2)
|
Note:
-
When A1-02 = 8 [Control Method Selection = EZOLV], the default setting changes when the setting for E9-01 [Motor Type Selection] and the drive model change.
-
E9-01 = 0 [Induction (IM)]
-
E9-01 = 1, 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]: 1
-
When you set A1-02 = 8 and E9-01 = 1 or 2, set b3-24 = 1. If b3-24 = 2, the drive will detect oPE08 [Parameter Selection Error].
-
When you set b3-24, it will trigger the drive to initialize b3-14 [Bi-directional Speed Search]. After you set b3-24, set b3-14.
Set b3-01 = 1 [Speed Search at Start Selection = Enabled] to do Speed Search at start. Set L2-01 = 1 [Power Loss Ride Through Select = Enabled for L2-02 Time]] to do Speed Search after you restore power after a momentary power loss.
- 1
- Speed Estimation
-
The drive uses the residual voltage from a short baseblock time to estimate the motor speed.
If there is not sufficient residual voltage, then the drive will inject DC current into the motor to estimate the motor speed.
- 2
- Current Detection 2
-
The drive will inject DC current into the motor to estimate motor speed.