No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b3-54
(3123)
|
Search Time
|
   
Sets the length of time that the drive will run Speed Search.
|
400 ms
(10 - 2000 ms)
|
If you set this parameter too low, Speed Search will not operate correctly.
If the drive detects oC [Overcurrent] immediately after Speed Search Starts:
-
Increase the value of L2-03 [Minimum Baseblock Time] and decrease the motor speed you use to start Speed Search.
-
Increases the setting value of b3-08 [Speed Estimation ACR P Gain].
-
Increase the value of b3-54.
If the drive detects oC or ov [DC Bus Overvoltage] during Speed Search, increase the value of b3-08.