No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b5-10
(01AE)
RUN
|
PID Output Gain Setting
|
   
Sets the amount of gain to apply to the PID output.
|
1.00
(0.00 - 25.00)
|
Applies a gain to the PID output and can help when b5-01 = 3 or 4 [PID Mode Setting = Fref + PID Trim, Fref + PID Trim (D on feedback)].