No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b5-34
(019F)
RUN
|
PID Output Lower Limit Level
|
   
Sets the lower limit level for the PID control as a percentage of E1-04 [Maximum Output Frequency].
|
0.0%
(-100.0 - +100.0%)
|
Use a lower limit to keep PID control output from dropping below a fixed level.
When you use b5-34, set b5-91 = 0 [EZ Sleep Minimum Speed = 0 (Disabled)].
When you set the output lower limit level in Hz or min-1 (r/min), refer to b5-91: EZ Sleep Minimum Speed.
Set this parameter to 0.0% to disable this function.