b5-53

(0B8F)

RUN

PID Integrator Ramp Limit

Sets the responsiveness of PID control when the PID feedback changes quickly.

0.0 Hz

(0.0 - 10.0 Hz)

Note:
  • This parameter is disabled when set to 0.0 Hz.

  • When b5-53 > 0.0 Hz and the drive enables the integrator ramp limit, the PID integrator value limit is the range set by the output frequency ± b5-53.