No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b5-58 to b5-60:
(1182 - 1184)
RUN
|
PID Setpoints 2 to 4
|
   
Sets the PID setpoint when H1-xx = 3E or 3F [MFDI Function Selection = PID Setpoint Selection 1/2]. This value is a percentage of the maximum output frequency.
|
0.00%
(0.00 - 100.00%)
|
Table 1 shows how the different MFDI H1-xx values (3E and 3F) have an effect on the PID setpoint value.
Table 1. Switching of MFDI and PID Setpoint Value
|
H1-xx = 3E
|
H1-xx = 3F
|
PID Setpoint Value
|
|
OFF
|
OFF
|
No switch
|
|
ON
|
OFF
|
b5-58 [PID Setpoint2]
|
|
OFF
|
ON
|
b5-59 [PID Setpoint3]
|
|
ON
|
ON
|
b5-60 [PID Setpoint4]
|