No.

(Hex.)

Name

Description

Default

(Range)

b5-58 to b5-60:

(1182 - 1184)

RUN

PID Setpoints 2 to 4

Sets the PID setpoint when H1-xx = 3E or 3F [MFDI Function Selection = PID Setpoint Selection 1/2]. This value is a percentage of the maximum output frequency.

0.00%

(0.00 - 100.00%)

Table 1 shows how the different MFDI H1-xx values (3E and 3F) have an effect on the PID setpoint value.

Table 1. Switching of MFDI and PID Setpoint Value

H1-xx = 3E

H1-xx = 3F

PID Setpoint Value

OFF

OFF

No switch

ON

OFF

b5-58 [PID Setpoint2]

OFF

ON

b5-59 [PID Setpoint3]

ON

ON

b5-60 [PID Setpoint4]