No.

(Hex.)

Name

Description

Default

(Range)

b6-03

(01B8)

Dwell Reference at Stop

Sets the output frequency that the drive will hold momentarily when ramping to stop the motor.

0.0

(Determined by A1-02)

When the drive decelerates to the output frequency set in b6-03, it holds that frequency for the time set in b6-04 [Dwell Time at Stop] and starts to decelerate again.