No.

(Hex.)

Name

Description

Default

(Range)

b8-06

(01D1)

Expert

Search Operation Voltage Limit

Sets the voltage limit for Search Operation as a percentage of the motor rated voltage.

0%

(0 - 100%)

The Search Operation changes the output voltage in small increments to find a setpoint at which the drive can use minimum power to operate.

Set this parameter to 0 to disable Search Operation. This will not disable Energy-saving control.

If the setting value is too low, the motor will stall when loads suddenly increase.