No.

(Hex.)

Name

Description

Default

(Range)

b8-17

(01F9)

Expert

PM E-Save Coefficient Kt

Sets torque linearity. This parameter uses the Kt value from the motor nameplate. Usually it is not necessary to change this setting.

1.00

(0.00 - 3.00)

When E5-01 = 1xxx [PM Motor Code Selection = Yaskawa SSR1 series IPM motor], the drive automatically calculates the energy-saving coefficient Kt and uses that value to control operation.

Do this procedure to prevent oscillation when you set b8-01 = 1 [Energy Saving Control Selection = Enabled].

  1. Check U5-22 [Energy Save Coeff Kt] and make sure that it aligns with the Kt value on the motor nameplate.

  2. If the numbers are different, set b8-17 to the Kt value on the motor nameplate.