No.

(Hex.)

Name

Description

Default

(Range)

C3-01

(020F)

RUN

Slip Compensation Gain

Sets the gain for the slip compensation function. Usually it is not necessary to change this setting.

Determined by A1-02

(0.0 - 2.5)

Note:

Correctly set these parameters before changing the slip compensation gain:

  • E2-01 [Motor Rated Current (FLA)]

  • E2-02 [Motor Rated Slip]

  • E2-03 [Motor No-Load Current]

Adjust this parameter as follows if necessary:

  • If the motor speed is slower than the frequency reference, increase this parameter in 0.1-unit increments.

  • If the motor speed is slower than the frequency reference value, decrease this parameter value in 0.1-unit increments.