No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
C3-21
(033E)
RUN
|
Motor 2 Slip Compensation Gain
|
   
Sets the gain for the motor 2 slip compensation function. Usually it is not necessary to change this setting.
|
Determined by E3-01
(0.0 - 2.5)
|
Note:
Correctly set these parameters before you change the slip compensation gain:
-
E4-01 [Motor 2 Rated Current]
-
E4-02 [Motor 2 Rated Slip]
-
E4-03 [Motor 2 Rated No-Load Current]
Adjust this parameter as follows if necessary:
-
If the motor speed is slower than the frequency reference, increase C3-01 in 0.1-unit increments.
-
If the motor speed is faster than the frequency reference, decrease C3-01 in 0.1-unit increments.