C3-24
(0243)
|
Motor 2 Slip Comp during Regen
|
   
Sets the slip compensation during regenerative operation function for motor 2.
|
0
(0 - 2)
|
If you apply a regenerative load when the slip compensation function during regeneration is active, the quantity of regeneration can increase immediately. In this condition, it is necessary to use a dynamic braking option (braking resistor or braking resistor unit).
- 0
- Disabled
-
The drive will not do Slip compensation during regeneration.
The load and operation status (regenerative operation) can cause the motor speed to be higher or lower than the frequency reference.
- 1
- Enabled Above 6Hz
-
Slip compensation function is enabled during regeneration. Slip compensation is disabled at output frequencies of 6 Hz or less.
- 2
- Enabled Above Defined Range
-
The drive uses E2-02 [Motor Rated Slip] to automatically calculate the frequency range where it will disable slip compensation function during regenerative operation.
Slip compensation is enabled at frequencies as low as 2 Hz.