Speed and torque are not stable at low speed.
|
Decrease the carrier frequency.
|
|
Speed and torque are not stable at low speed.
|
Decrease the carrier frequency.
|
|
Too much leakage current from the drive.
|
Decrease the carrier frequency.
|
|
Wiring between the drive and motor is too long.
|
Decrease the carrier frequency.
Note:
If the motor cable is too long, it can be necessary to decrease the carrier frequency. Refer to Table 2 for the wiring distance and decrease the carrier frequency.
|
|
Audible motor noise is too loud.
|
Increase the carrier frequency. Use Swing PWM.
Note:
The default carrier frequency in ND is C6-02 = 7 [Swing PWM1 (Audible Sound 1)], with a 2 kHz base. You can increase the carrier frequency in Normal Duty mode, but this will decrease the drive rated current.
|