No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
C6-09
(022B)
|
Carrier Freq at Rotational Tune
|
   
Sets the Auto-Tuning carrier frequency. Usually it is not necessary to change this setting.
|
0
(0, 1)
|
If C6-09 = 0 and you do Auto-Tuning on a high frequency motor or low impedance motor, it can cause oC [Overcurrent]. To prevent oC, increase the carrier frequency value, set C6-09 = 1, then do Auto-Tuning.
The procedure to set the carrier frequency when the A1-02 [Control Method Selection] setting changes.
-
When A1-02 = 2 [OLV], set C6-02 = F [Carrier Frequency Selection = User Defined (C6-03 to C6-05)] and then increase the value set to C6-03 [Carrier Frequency Upper Limit].
-
When A1-02 = 5 or 6 [OLV/PM or AOLV/PM], use C6-02 to increase the carrier frequency.
- 0
- 5 kHz
-
Note:
When A1-02 = 5 or 6, the carrier frequency is 2 kHz.
- 1
- Use C6-03
-
Note:
When A1-02 = 5 or 6, the carrier frequency is the value set to C6-02.