YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
d1-01
(0280)
RUN
Reference 1
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values change. Calculate the upper limit value with this formula:
Upper limit value = (E1-04) × (d2-01) / 100
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].