d1-01: Reference 1

No.

(Hex.)

Name

Description

Default

(Range)

d1-01

(0280)

RUN

Reference 1

Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].

0.00 Hz

(0.00 - 590.00 Hz)

Note:
  • The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values change. Calculate the upper limit value with this formula:

    Upper limit value = (E1-04) × (d2-01) / 100

  • When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].