d4-06: Frequency Ref Bias (Up/Down 2)

No.

(Hex.)

Name

Description

Default

(Range)

d4-06

(02AD)

Frequency Ref Bias (Up/Down 2)

Saves the bias value from the Up/Down 2 Command where the Maximum Output Frequency is 100%.

0.0%

(-99.9 - +100.0%)

The Up/Down 2 function setting changes the function of d4-06:

Note:

When the keypad sets the frequency reference, you do not usually use parameter d4-06.

  • When d4-01 = 0 [Freq Reference Hold Selection = Disabled] and a source other than the keypad sets the frequency reference, the drive adds the value set in d4-06 to the frequency reference. If the value set in d4-06 is a negative number, the drive will subtract it from frequency reference.

  • When d4-01 = 1 [Enabled] and a source other than the keypad sets the frequency reference, the drive will store the bias value adjusted with the Up/Down 2 command in d4-06 5 seconds after you release the Up/Down 2 command. The drive adds or subtracts the value set in d4-06 to the frequency reference.

Conditions that Reset or Disable d4-06

The drive resets and disables the bias value in these conditions:

  • d4-01 = 0 and the Run command was cleared.

  • H1-xx = 75, 76 [MFDI Function Select = Up/Down 2 Command] is not set.

  • The frequency reference source was changed.

    This includes switching LOCAL/REMOTE and multi-step speed reference.

  • A digital input changed the frequency reference value.

  • d4-03 [Up/Down 2 Bias Step Frequency] = 0 and d4-05 = 1 [Up/Down 2 Bias Mode Selection = Reset when Neither / Both Closed], and the two MFDI terminals set for Up/Down 2 Command [H1-xx = 75/76] are activated or deactivated.

  • The value of E1-04 [Maximum Output Frequency] was changed.