No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
d4-08
(02AF)
RUN
|
Up/Down 2 Bias Upper Limit
|
   
Sets the upper limit of the Up/Down 2 bias as a percentage of the Maximum Output Frequency.
|
100.0%
(0.0 - 100.0%)
|
The drive saves the set bias upper limit in d4-06 [Frequency Ref Bias (Up/Down 2)]. Set d4-08 an applicable value before you use the Up/Down 2 function.
Note:
When d4-01 = 1 [Freq Reference Hold Selection = Enabled] and b1-01 = 0 [Frequency Reference Selection 1 = Keypad], the drive will add the bias value to the frequency reference when it does not receive an Up/Down 2 command for 5 s. Then the drive will reset the value to 0 at which time you can increase the bias to the limit set in d4-08 again.