No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
d4-09
(02B0)
RUN
|
Up/Down 2 Bias Lower Limit
|
   
Sets the lower limit of the Up/Down 2 bias as a percentage of the Maximum Output Frequency.
|
0.0%
(-99.9 - 0.0%)
|
The drive saves the set bias lower limit in d4-06 [Frequency Ref Bias (Up/Down 2)]. Set d4-09 to an applicable value before you use the Up/Down 2 function.
Note:
When d4-01 = 1 [Freq Reference Hold Selection = Enabled] and b1-01 = 0 [Frequency Reference Selection 1 = Keypad], the drive will add the bias value to the frequency reference when it does not receive an Up/Down 2 command for 5 s. Then the drive will reset the value to 0.
If you increase the bias with the Up 2 command and d4-09 = 0, you cannot use a Down 2 command to decrease the frequency reference. To decrease speed in this condition, set a negative lower limit in d4-09.