E1-01
(0300)
Input AC Supply Voltage
Sets the drive input voltage.
200 V Class: 200 V,
(200 V Class: 155 to 255 V, 400 V Class: 310 to 510 V)
The value set in E1-01 is the base value that the drive uses for the motor protective functions in Table 1. With a 400 V class drive, the detection level changes for some motor protective functions.
Voltage
E1-01 Setting
Approximate Values
ov Detection Level
BTR Operation Level
(rr Detection Level) 1
L2-05
[Undervoltage Detection Lvl (Uv1)]
L2-11
[KEB DC Bus Voltage Setpoint]
L3-17
[DC Bus Regulation Level]
200 V Class
All settings
410 V
394 V
190 V
260 V
375 V
400 V Class
Setting value ≥ 400 V
820 V
788 V
380 V
500 V
750 V
Setting value < 400 V
350 V
460 V