YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
E1-13
(030C)
Expert
Base Voltage
Sets the base voltage for the V/f pattern.
0.0 V
(200 V Class: 0.0 - 255.0 V,400 V Class: 0.0 - 510.0 V)
After Auto-Tuning, the value of E1-13 = E1-05 [Maximum Output Voltage].
When E1-13 = 0.0, use the value of E1-05 to control the voltage.