No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
E2-01
(030E)
|
Motor Rated Current (FLA)
|
   
Sets the motor rated current in amps.
|
Determined by o2-04, C6-01
(10% to 200% of the drive rated current)
|
Note:
-
If E2-01 < E2-03 [Motor No-Load Current], the drive will detect oPE02 [Parameter Range Setting Error].
-
When the drive model changes, the display units for this parameter also change.
-
0.01 A: B001 to B018, 2001 to 2042, 4001 to 4023
-
0.1 A: 2056 to 2082, 4031 to 4060
The value set for E2-01 becomes the reference value for motor protection and the torque limit. Enter the motor rated current written on the motor nameplate. Auto-Tuning the drive will automatically set E2-01 to the value input for T1-04 [Motor Rated Current].