Jump to main content

E2-05: Motor Line-to-Line Resistance

No.

(Hex.)

Name

Description

Default

(Range)

E2-05

(0312)

Motor Line-to-Line Resistance

Sets the line-to-line resistance for the motor stator windings.

Determined by o2-04, C6-01

(0.000 - 65.000 Ω)

Note:

This value is the motor line-to-line resistance. Do not set this parameter with the resistance per phase.

Auto-Tuning automatically sets this parameter. If you cannot do Auto-Tuning, use the test report from the motor manufacturer to configure the settings. Use one of these formulas to calculate the motor line-to-line resistance:

  • E-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.822

  • B-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.822

  • F-type insulation: [the resistance value (Ω) shown on the test report at 115 °C] × 0.728