No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
E4-01
(0321)
|
Motor 2 Rated Current
|
   
Sets the motor rated current for motor 2 in amps.
|
Determined by o2-04, C6-01
(10% to 200% of the drive rated current)
|
Note:
-
If E4-01 ≤ E4-03 [Motor 2 Rated No-Load Current], the drive will detect oPE02 [Parameter Range Setting Error].
-
When the drive model changes, the display units for this parameter also change.
-
0.01 A: B001 - B018, 2001 - 2042, 4001 - 4023
-
0.1 A: 2056 - 2082, 4031 - 4060
The value set for E4-01 becomes the reference value for motor protection, the torque limit, and torque control. Enter the motor rated current written on the motor nameplate. Auto-Tuning automatically sets the value of E4-01 to the value input for [Motor Rated Current].