E4-01: Motor 2 Rated Current

No.

(Hex.)

Name

Description

Default

(Range)

E4-01

(0321)

Motor 2 Rated Current

Sets the motor rated current for motor 2 in amps.

Determined by o2-04, C6-01

(10% to 200% of the drive rated current)

Note:
  • If E4-01 ≤ E4-03 [Motor 2 Rated No-Load Current], the drive will detect oPE02 [Parameter Range Setting Error].

  • When the drive model changes, the display units for this parameter also change.

    • 0.01 A: B001 - B018, 2001 - 2042, 4001 - 4023

    • 0.1 A: 2056 - 2082, 4031 - 4060

The value set for E4-01 becomes the reference value for motor protection, the torque limit, and torque control. Enter the motor rated current written on the motor nameplate. Auto-Tuning automatically sets the value of E4-01 to the value input for [Motor Rated Current].