No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
E4-03
(0323)
|
Motor 2 Rated No-Load Current
|
   
Sets the no-load current for motor 2 in amps when operating at the rated frequency and the no-load voltage.
|
Determined by o2-04, C6-01
(0 to E4-01)
|
Note:
When the drive model changes, the display units for this parameter also change.
-
0.01 A: B001 - B018, 2001 - 2042, 4001 - 4023
-
0.1 A: 2056 - 2082, 4031 - 4060
You can also manually enter the motor no-load current shown on the motor test report to E4-03. Contact the motor manufacturer for the motor test report.
Note:
The default setting of the no-load current is for a 4-pole motor recommended by Yaskawa.