Jump to main content

E4-09: Motor 2 Mechanical Loss

No.

(Hex.)

Name

Description

Default

(Range)

E4-09

(033F)

Expert

Motor 2 Mechanical Loss

Sets the mechanical loss of motor 2. It is set as a percentage of E4-11 [Motor 2 Rated Power]. Usually it is not necessary to change this setting.

0.0%

(0.0 - 10.0%)

Adjust this parameter in these conditions. The drive adds the configured mechanical loss to the torque reference value as a torque compensation value:

  • There is a large quantity of torque loss from motor bearing friction.

  • There is a large quantity of torque loss in fans and pumps.