E5-05: PM Motor Resistance (ohms/phase)

No.

(Hex.)

Name

Description

Default

(Range)

E5-05

(032D)

PM Motor Resistance (ohms/phase)

Sets the resistance per phase of a PM motor. Set 50% of the line-to-line resistance.

0.100 Ω

(0.000 - 65.000 Ω)

PM motor Auto-Tuning automatically sets this parameter to the value of [PM Motor Stator Resistance].

Note: