No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
E5-05
(032D)
|
PM Motor Resistance (ohms/phase)
|
   
Sets the resistance per phase of a PM motor. Set 50% of the line-to-line resistance.
|
0.100 Ω
(0.000 - 65.000 Ω)
|
PM motor Auto-Tuning automatically sets this parameter to the value of [PM Motor Stator Resistance].
Note:
Do not change the setting calculated by Auto-Tuning unless it is necessary.