Jump to main content

F1-14: Encoder Open-Circuit Detect Time

No.

(Hex.)

Name

Description

Default

(Range)

F1-14

(038D)

Encoder Open-Circuit Detect Time

Sets the length of time that the drive must not receive a pulse signal to cause PGo [Encoder (PG) Feedback Loss].

2.0 s

(0.0 - 10.0 s)

If the drive does not detect ouput pulses from the encoder for the time set in F1-14, it will trigger PGo.

Note:
  • When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.

  • Motor speed and load conditions can cause ov [Overvoltage] and oC [Overcurrent] faults.