Setting Value
|
Function
|
Description
|
|
0
|
3-Wire Sequence
|
   
Sets the direction of motor rotation for 3-wire sequence.
|
If the 3-wire sequence is set to a terminal that is not MFDI terminals S1 and S2, these terminals will be the input terminals for Forward run/Reverse run command. The drive will automatically set terminal S1 to Run command (RUN) and terminal S2 to Stop command (STOP).
When terminal S1 (Run command) activates for 1 ms minimum, the drive rotates the motor. When terminal S2 (Stop command) deactivates, the drive stops. When terminal Sx that is set in 3-wire sequence deactivates, the drive operates in the forward direction, and when it activates, the drive operates in the reverse direction.
| Warning |
|
Sudden Movement Hazard
Set the MFDI parameters before you close control circuit switches.
Incorrect Run/Stop circuit sequence settings can cause serious injury or death from moving equipment.
|
| Warning |
|
Sudden Movement Hazard
When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize Parameters = 3-Wire Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] (default).
If you do not correctly set the drive parameters for 3-Wire operation before you energize the drive, the motor can suddenly rotate when you energize the drive.
|
Figure 1. 3-Wire Sequence Wiring Example
.
Figure 2. 3-Wire Sequence Time Chart
Note:
-
To input the Run command, activate the terminal for 1 ms minimum.
-
The default setting for b1-17 [Run Command at Power Up] is 0 [Disregard existing RUN command]. If you enable the Run command on an energized drive, the protective function activates and the
flashes quickly. When the application will let an energized drive Run, set b1-17 = 1 [Accept Existing RUN Command].