Jump to main content

13: Reverse Jog

Setting Value

Function

Description

13

Reverse Jog

Sets the command to operate the motor in the reverse direction at the Jog Frequency set in d1-17 [Jog Reference].

Note:
  • It is not necessary to input the Run command.

  • The Reverse JOG command has priority over all other frequency references.

  • When the Forward JOG and Reverse JOG commands are activated at the same time for 500 ms or longer, the drive will ramp to stop.