YASKAWA AC Drive GA700 High Performance Type Technical Manual
Setting Value
Function
Description
20 to 2F
External Fault
Sets a command to stop the drive when a failure or fault occurs on an external device.
If an external fault is input to the drive, the keypad will show EFx [External Fault (Terminal Sx)], where x is the number of the terminal (terminal Sx) to which the external fault signal is assigned. For example, when an external fault signal is input to terminal S3, the keypad will show EF3 [External Fault (Terminal S3)].
Use these conditions to select the value to set in H1-xx:
Signal input method from peripheral devices
External fault detection method
Motor stopping method (operation after external fault detection)
Table 1 shows the relation between the conditions and the value set to H1-xx.
Setting
Signal Input Method from Peripheral Devices 1
External Fault Detection Method 2
Stopping Method
N.O.
N.C.
Always Detected
Detected during RUN Only
Ramp to Stop (Fault)
Coast to Stop (Fault)
Fast Stop (Fault)
Continuous Operation (Alarm Only)