YASKAWA AC Drive GA700 High Performance Type Technical Manual
Setting Value
Function
Description
40
Forward RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 41 [Reverse RUN (2-Wire)] together.
If you turn ON the Forward Run command terminal and the Reverse Run command terminal, it will cause an EF [FWD/REV Run Command Input Error] alarm and the motor will ramp to stop.
Initialize the drive with a 2-wire sequence to set the Forward Run command to terminal S1.