Jump to main content

41: Reverse RUN (2-Wire)

Setting Value

Function

Description

41

Reverse RUN (2-Wire)

Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 40 [Forward RUN (2-Wire)] together.

ON
Reverse Run
 
OFF
Stop
 
Note:
  • If you turn ON the Forward Run command terminal and the Reverse Run command terminal, it will cause an EF [FWD/REV Run Command Input Error] alarm and the motor will ramp to stop.

  • Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal S2.

  • This function will not operate at the same time as H1-xx = 42, 43 [Run Command (2-Wire Sequence 2), FWD/REV (2-Wire Sequence 2)].