Setting Value
Function
Description
61
Speed Search from Fmax
Sets the function to use an external reference to start speed search although b3-01 = 0 [Speed Search Selection at Start = Disabled] to not allow speed search at start.
When the terminal is activated for b3-24 = 2 [Speed Search Method Selection = Current Detection 2], the drive starts speed search from the maximum output frequency.
The drive will detect oPE03 [Multi-Function Input Setting Err] if you set H1-xx = 61 and H1-xx = 62 at the same time.