Setting Value
|
Function
|
Description
|
|
65
|
KEB Ride-Thru 1 Activate (N.C.)
|
   
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.C.).
|
- ON
- Normal operation
-
- OFF
- Deceleration during momentary power loss
-
When you enable KEB Ride-Thru 1, set L2-29 [KEB Method Selection]. The drive operates with the selected KEB method.
Note:
-
If you set KEB Ride-Thru 1 [H1-xx = 65, 66] and KEB Ride-Thru 2 [H1-xx = 7A, 7B] at the same time, the drive will detect oPE03 [Multi-Function Input Setting Err].
-
Refer to KEB Ride-Thru Function for more information.